Powered by Perkins 1106D-E70TAG3
Emissions: Tier 3 EPA Certified — Emergency Stationary Applications
60 Hz Power Rating, 3-Phase
Standby Power Rating: 191 kVA / 153 kW
Prime Power Rating: 170 kVA / 136 kW
Leroy Somer Alternator
Deep Sea DSE 7420 Control Panel
UL2200 Listed
Americas Generators provides Emergency Stationary generators certified to Tier 4i, Tier 3, and Tier 2 ratings, with UL2200, CSA, and other compliance options. Triton can build virtually any generator to spec — gaseous or diesel — and we maintain ready stock of generators built to standard configurations for immediate shipment, along with trailers, transfer switches, and fuel tanks.
Triton EPA Generators are engineered to exacting standards for the US and Canadian markets. We offer options for everything from hurricane zones along the Gulf coast to the harsh climate of the far north. Triton generators are deployed at government facilities, hotels, manufacturing plants, medical facilities, grocery stores, and data centers across North America.
The TP-P150-T3-UL delivers a standby rating of 153 kW / 191 kVA and a prime rating of 136 kW / 170 kVA. The Perkins 1106D-E70TAG3 is a six-cylinder, turbocharged and air-to-air aftercooled diesel engine engineered for high-output performance and Tier 3 emissions compliance in modern power generation applications. Operating at 1800 rpm, it delivers 178 kWm (239 hp), offering excellent fuel efficiency, strong power density, and long-term durability. At Triton Power, we rely on engines like the Perkins 1106D-E70TAG3 because they provide consistent power delivery, reduced environmental impact, and dependable global parts and service support—making them a trusted solution for demanding commercial and industrial generator sets. The Perkins 1106D-E70TAG3 pairs with a Leroy Somer alternator, and the Deep Sea DSE 7420 digital control panel makes monitoring and management straightforward. The TP-P150-T3-UL is built to rugged specifications and delivers power exactly where and when you need it.
Standard Features
The TP-P150-T3-UL includes the following standard features:
Why Triton
Triton EPA Generators are compliant for emergency stationary use throughout the United States and Canada. Our generators are engineered to operate in the most challenging environments and can be modified to meet virtually any application. With standalone models ranging from 10 kW to 2,500 kW, paralleled generators up to 20 MW, and the ability to customize a unit to fit any need, your options for durable and reliable power generation are essentially unlimited. That’s why for over 30 years, Americas Generators has been the name to trust when you need dependable power.
| Triton Model | TP-P150-T3-UL |
| Engine Brand | Perkins |
| Engine Model | 1106D-E70TAG3 |
| Engine Tier Rating | Tier 3 |
| Engine Power Output | 178 kWm / 239 HP @ 1800 RPM |
| Aspiration | Turbocharged Aftercooled |
| Displacement | 7.01 L |
| Cylinders | 6, in line |
| Alternator Brand | Leroy Somer |
| Alternator Model | LSA44.3L12 |
| Insulation Class | H |
| Typical Generator Output | Standby: 191 kVA / 153 kW Prime: 170 kVA / 136 kW |
| Frequency | 60 Hz |
| Speed | 1800 RPM |
| Control Panel | Deep Sea DSE 7420 |
| Voltages Available | 120/208, 277/480 |
| Models Available | Enclosed, Open Skid |
| Compliance | UL 2200 Listed, EPA Tier 3, NFPA 110 compatible |